Wastewater Treatment Systems - page 32

32 •
Oil/Sand Interceptor Sizing Guide
Flow
Total
Recommended
Inlet &
Model
Rate
Volume
Oil Pump-out
Outlet
OSI
Gal/Min
Gallons
Gallons
Diameter
Length
Diameter
*350
35
350
88
3'-6"
4'-3"
4"
**550
55
550
138
3'-6"
7'-9"
4"
750
75
750
188
4'-0"
8'-0"
6"
1,000
100
1,000
250
4'-0"
10'-9"
6"
1,500
150
1,500
375
5'-4"
9'-0"
6"
2,000
200
2,000
500
5'-4"
12'-0"
6"
3,000
300
3,000
750
5'-4"
18'-0"
8"
4,000
400
4,000
1,000
5'-4"
24'-0"
8"
5,000
500
5,000
1,250
6'-0"
23'-10"
8"
6,000
600
6,000
1,500
6'-0"
28'-8"
10"
7,000
700
7,000
1,750
7'-0"
24'-4"
10"
8,000
800
8,000
2,000
7'-0"
28'-0"
10"
9,000
900
9,000
2,250
8'-0"
24'-0"
12"
10,000
1,000
10,000
2,500
8'-0"
26'-8"
12"
12,000
1,200
12,000
3,000
8'-0"
32'-0"
12"
15,000
1,500
15,000
3,750
10'-0"
25'-6"
14"
20,000
2,000
20,000
5,000
10'-6"
31'-0"
16"
25,000
2,500
25,000
6,250
10'-6"
38'-9"
18"
30,000
3,000
30,000
7,500
10'-6"
46'-6"
20"
40,000
4,000
40,000
10,000
12'-0"
47'-3"
24"
50,000
5,000
50,000
12,500
12'-0"
59'-0"
24"
60,000
6,000
60,000
15,000
13'-0"
60'-6"
24"
Note: NPT available for 4-6" inlet and outlet; 8" and larger will be flanged connections. Optional sampling/monitoring ports available.
*Available as single basin ONLY with one manway. **Available as single and double basin ONLY with one manway.
† Not available on all sizes, contact Highland Tank for more information.
Diameter
Length
Flanged
Inlet Pipe
Inlet Vent
Outlet Vent
Sludge
Baffle
Wear Plate
Striker
Plate
OUTLET
INLET
Flanged
Outlet Pipe
Underflow
Baffle
Velocity Head
Diffusion Baffle
Vent Fitting
24" Dia.
Manways
Sensor Fitting
Dimensions
1...,22,23,24,25,26,27,28,29,30,31 33,34,35,36,37,38,39,40,41,42,...58