Wastewater Treatment Systems - page 35

• 35
How It Works
Drainage Required
Flow
Total
Sediment
Inlet &
Model
Area *WQTV
Rate
Volume
Volume
Dimensions Outlet
SSI
Acres Gallons
Gal/Min-Ft
3
/s Gallons
Ft
3
Dia / Length Diameter
2,000
.125
1,700
300 - 0.668
2,000
186.2
5'-4" x 12'-0"
6"
4,000
.25
3,400
500 - 1.114
4,000
361.7
5'-4" x 24'-0"
8"
8,000
.50
6,800
1,000 - 2.228
8,000
746.2
8'-0" x 21'-4"
10"
12,000
.75 10,200
1,500 - 3.342
12,000
1,128.5
10'-0" x 20'-6"
12"
15,000
1.00 13,600
1,700 - 3.787
15,000
1,382.1
10'-0" x 25'-6"
14"
20,000
1.25 17,000
2,500 - 5.570
20,000
1,836.8
10'-6" x 31'-0"
16"
25,000
1.50 20,400
3,000 - 6.684
25,000
2,312.3
10'-6" x 38'-9"
18"
30,000
2.00 27,200
3,500 - 7.798
30,000
2,710.2
10'-6" x 46'-6"
18"
40,000
2.50 34,000
4,500 - 10.026
40,000
3,551.0
12'-0" x 47'-9"
24"
50,000
3.00 40,800
5,200 - 11.585
50,000
4,425.1
12'-0" x 59'-6"
24"
60,000
4.00 54,400
6,100 - 13.591
60,000
5,361.5
13'-0" x 60'-6"
24"
Standard SSI will provide efficient removal of pollutant particles (.50
"
inch solids/sieve size 200 sediment) for the majority of site conditions.
WQTV* is the Water Quality Treatment Volume ("FirstFlush") or the first .50" of rain water runoff from the drainage area. 24" dia. manways
are standard; 30", 36", and large rectangular EZ-Access manways are available.
Solids Interceptor Sizing Guide
Solids Collection
Sediment Baffle
Sediment Weir
Sludge Baffle
Outlet Pipe
Access Manways
Inlet Pipe
HighGuard
Protection
System
Concrete Deadmen Anchors
or Hold-Down Pad
Hold-Down Straps
Secondary Floating Solids Interceptor Screen
Internal
Lining
Velocity Head Diffusion Screen