Wastewater Treatment Systems - page 37

• 37
Manual Oil Interceptors Sizing Guide
MEMBER
CL
Waste Oil
*Flow
Total
**
Inlet & Inlet &
Storage
Model
Rate
Volume
Outlet
Outlet
Compartment
MOI Gal/Min Gallons Ft.
3
Length Width Height
NPT Height
Width Volume
25
25
55.2
7.4
26"
20"
34"
3"
26"
17.25"
50
35
35
74.7
10.0
32"
22"
34"
3"
26"
14.00"
50
50
50
80.8
10.8
32"
22"
36"
3"
28"
25.75"
100
75
75 168.9
22.6
46"
32"
36"
3"
28"
18.00"
100
100
100 187.5
25.1
49"
34"
36"
4"
28"
33.00"
200
125
125 195.2
26.1
51"
34"
37"
4"
28"
33.00"
200
150
150 214.3
28.6
56"
34"
38"
4"
28"
29.50"
200
200
200 291.4
39.o
66"
34"
42"
4"
32"
33.00"
300
250
250 426.4
57.0
72"
38"
50"
4"
38"
22.75"
300
300
300 511.3
68.3
76"
42"
52"
4"
40"
25.50"
300
350
350 549.7
73.5
78"
44"
52"
4"
40"
37.00"
500
400
400 621.3
83.1
80"
46"
54"
4"
42"
34.375"
500
450
450 664.5
88.8
82"
48"
54"
4"
42"
33.50"
500
500
500 781.8 104.5
84"
50"
58"
4"
46"
30.00"
500
* Intermittent flow. **NPT 6" and larger – companion flanged connection. Also available with 8" or 10" inlet or outlet. “No-Hub"
connections can be supplied for floor mounting or partially recessed installations. Note: Vent Connections are 2" or 3" NPT,
on outlet end of MOI. Check and advise for local code requirements. Contact your local Highland representative for assistance
with the local Authority Having Jurisdiction (AHJ) regulations.
Width
Length
Polyurethane
Coated
Carbon
Steel
Vent Fitting
Sludge
Baffle
OUTLET
INLET
Under Flow
Diffusion Baffle
Compartment
Width
Height
Inlet / Outlet
Height
Skimmer Fitting
Waste Oil
Compartment
Indirect Flow
Transfer Baffle
"No-Hub"
Inlet/Outlet
Bolt-on painted carbon steel deck plate cover with
flush-mount lifting eyes for light foot traffic ONLY
MOI-SO - with Side Oil Compartment
MOI
Adjustable
Oil Skimmer
Dimensions
Concrete
Anchors
1...,27,28,29,30,31,32,33,34,35,36 38,39,40,41,42,43,44,45,46,47,...58