ASME Pressure Vessels and Water Storage Tanks - page 58

Tank Saddles
UL Saddles
UL Saddles are designed for a specific
diameter horizontal storage tank and
fabricated to the latest UL-142 design
standards. They can be welded directly
to the tank or shipped loose.
Saddle Features
‹‹ Heavy-duty UL-142 steel construction
for long-term durability
‹‹ Standard saddles provide 6" of
clearance and are available up to 12"
high. Saddles higher than 12" must
be protected with a fire resistant
material with a two-hour fire rating
‹‹ Only two properly positioned saddles
per tank required
‹‹ Four 1-1/8" diameter bolt holes are
provided to secure the saddles to the
concrete pad or piers
‹‹ Saddles are painted to the same
specifications as the tank
Secure Fluid Storage
Our tank saddles are used to provide
longitudinal support, maintain the
tank’s position and elevation and
help minimize corrosion. They also
provide clearance for complete visual
inspection of the underside of
the tanks.
Highland’s integral seal-welded tank
saddles are constructed in accordance
Underwriters’ Laboratories, Inc.
and designed to support the full load
of tank and contents. Our new two
saddle system is easy installation and
service. Additionally, the tank saddles
can be anchored to concrete pad
to help protect the tank from
movement or floatation.
Large Skids
Supports
Tank
Diameter
Length(L)
Width(W)
Front(F)
Side(S)
3'-2"
35"
8"
7.5"
2"
4'-0"
44"
8"
12"
2"
5'-4"
58"
8"
14"
2"
6'-0"
65"
8"
17.5"
2"
8'-0"
87"
10"
28.5"
2"
9'-0"
98"
10"
34"
2"
10'-0"
108"
10"
39"
2"
10'-6"
114"
10"
42"
2"
12'-0"
130"
12"
50"
3"
12'-6"
114"
10"
42"
2"
13'-0"
130"
12"
50"
3"
Base Plate Dimensions
Bolt Hole Locations
from Centerline
SS
Tank Saddle Assembly Specifications
To ensure adequate support on horizontal tanks,
follow the guidelines for saddle spacing.
SS
F
F
L
58 •
Saddles allow for visual inspection of the entire tank.
1...,48,49,50,51,52,53,54,55,56,57 59,60,61,62,63,64,65,66,67,68,...